On an HP R1500 G3 UPS configured with an HP Network Module Card (NMC), if the "Set Time Manually" radio button in the NMC Time settings window is selected, the time/date will default to 1970/01/01 if the UPS and NMC are shut down then restarted.This occurs because the R1500 G3 UPS does not have a real time clock (RTC) and the NMC normally receives the initial clock time after a restart from the UPS. The lack of RTC and the use of the manual setting require a manual reset of the time after each power-cycle. The R1500 G3 UPS does not provide auxiliary or standby power to the Network Module while the UPS is powered off.Note:This does not occur when using the "Set Time Manually" radio button on an HP R3000 G2, R5000, or R7000 UPS.
Any HP R1500 G3 UPS configured with a Network Module and using the "Set Time Manually" feature.
If using the "Set Time Manually" radio button, the time/date will require a manual reset after each power-cycle.To avoid this issue, use either the default "Accept Automatic Update from HPPP" setting or the "Synchronize with NTP Server" setting radio buttons.RECEIVE PROACTIVE UPDATES: Receive support alerts (such as Customer Advisories), as well as updates on drivers, software, firmware, and customer replaceable components, proactively via e-mail through HP Subscriber's Choice. Sign up for Subscriber's Choice at the following URL:http://www.hp.com/go/myadvisoryNAVIGATION TIP: For hints on navigating HP.com to locate the latest drivers, patches, and other support software downloads for ProLiant servers and Options, refer to theNavigation Tips document.
Operating Systems Affected:Not Applicable
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
BugZero Plan
Streamline upgrades with automated vendor bug scrubs
BugZero Prevent
Wish you caught this bug sooner? Get proactive today.