The HP UPS T1000 G2, T1500 G2, or R/T 2200 G2 Uninterruptible Power System output may become unstable when configured to the 100-volt range if connected to a ProLiant server in a redundant power supply configuration.This may cause the server to reboot when the main utility voltage goes offline and the UPS enters the ON BATTERY mode. In rare cases, a reset may occur when the server is configured with a single power supply.This occurs when the UPS has been set to the 100-volt configuration via the DIP switches located on the rear of the UPS. In this instance, the UPS will be operating on the fringe of the normal server voltage range of 100 to 127 volts AC (VAC).Note:This issue has only been reported in Japan; where 100 volts is the standard utility voltage.
Any HP UPS T1000 G2, T1500 G2, or R/T 2200 G2 Uninterruptible Power System set to a 100- volt configuration and connected to a server in a redundant power supply configuration.
To ensure that the HP UPS T1000 G2, T1500 G2, R/T 2200 G2 inverter output remains stable and to prevent the server power supply from resetting the server, set the voltage configuration DIP switches on the rear of the UPS to 110 volts.For additional information and instructions, refer to the following user guides:HP UPS T1000/1500 User Guide, available at the following URL:https://support.hpe.com/hpesc/public/docDisplay?docId=c00708073HP R/T2200 UPS User Guide, available at the following URL:https://support.hpe.com/hpesc/public/docDisplay?docId=c00708012RECEIVE PROACTIVE UPDATES: Receive support alerts (such as Customer Advisories), as well as updates on drivers, software, firmware, and customer replaceable components, proactively via e-mail through HP Subscriber's Choice. Sign up for Subscriber's Choice at the following URL:http://www.hp.com/go/myadvisorySEARCH TIP: For hints on locating similar documents on HP.com, refer to the Search Tips document:https://support.hpe.com/hpesc/public/docDisplay?docId=c00638154.To search for additional advisories related to HP UPS T1000 G2, T1500 G2, R/T 2200 G2, use the following search string:+Advisory +UPS +"T1000 G2, T1500 G2, R/T 2200 G2"KEYWORDS: UPS, T1000, T1500, R/T2200, boot, restart, re-boot
Operating Systems Affected:Not Applicable
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
BugZero Plan
Streamline upgrades with automated vendor bug scrubs
BugZero Prevent
Wish you caught this bug sooner? Get proactive today.