Loading...
Loading...
The following issues have been corrected and enhancements made to both the high voltage and low voltage models of the Compaq R3000XR UPS by upgrading to firmware version 1.04:Addressed "Delay Restart Timer" issue in which the R3000XR did not start up per the delay restart times that were set using the Compaq Power Manager software.Addressed "Lockup issue with the Compaq ProLiant DL380 server" in which the server locked up and did not power on after utility was restored (i.e., utility power fails and the UPS switches to battery and the server and UPS safely shut down).Enhanced the communication internal to the UPS.Added instructions for OEM software.Enhanced the Connectivity Manager.
Any of the following Compaq R3000XR UPS models:192186-001 Low Voltage (North America / Latin America Models)192186-002 High Voltage (North America / Latin America Models)192186-291 Low Voltage (Japan Models)192186-292 High Voltage (Japan Models)192186-B31, 192186-B32, 192186-B33, 192186-AR1 High Voltage (International Models)
To obtain enhancements and correct or prevent the listed issues, upgrade the R3000XR UPS firmware to version 1.04 by applying SoftPaq SP18015. The SoftPaq can be downloaded at the following URL:ftp://ftp.compaq.com/pub/softpaq/sp18001-18500/sp18015.exeNote: Instructions for upgrading the R3000XR UPS firmware to version 1.04 are contained in SoftPaq SP18015.Downloadable SolutionsDownloadable FileLocationSP18015
Operating Systems Affected:Not Applicable
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
BugZero Plan
Streamline upgrades with automated vendor bug scrubs
BugZero Prevent
Wish you caught this bug sooner? Get proactive today.