The battery runtime for some HP R1500 XR UPS and HP T2200 XR Uninterruptible Power Systems may be erroneously displayed in HP Power Manager (HPPM).A small number of units configured with one Extended Runtime Module (ERM) were incorrectly programmed as though they contained two ERMs. This causes the UPS firmware to calculate an estimated runtime based on two ERMs. As a result, a longer battery runtime is reported in HPPM which may cause the software to incorrectly conduct a timely shutdown of the attached loads (servers).
HP R1500 XR UPS and HP T2200 XR Uninterruptible Power Systems configured with one Extended Runtime Module (ERM).
To ensure that accurate runtime predictions are reported to HPPM, run the ERM Configurator Utility Version 1.2.2 (or later) which is available for download from the HP Rack and Power Firmware and Drivers web site at the following URL:http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/software/hard-firmware.htmlRECEIVE PROACTIVE UPDATES: Receive support alerts (such as Customer Advisories), as well as updates on drivers, software, firmware, and customer replaceable components, proactively via e-mail through HP Subscriber's Choice. Sign up for Subscriber's Choice at the following URL:http://www.hp.com/go/myadvisorySEARCH TIP: For hints on locating similar documents on HP.com, refer to theSearch Tips document.To search for additional advisories related to HP Power Manager (HPPM) , use the following search string:+ProLiant +Advisory +HPPMKEYWORDS:UPS, HPPM, ERM, wrong
Operating Systems Affected:Not Applicable
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
BugZero Plan
Streamline upgrades with automated vendor bug scrubs
BugZero Prevent
Wish you caught this bug sooner? Get proactive today.