Loading...
Loading...
Any of the HPE G4 Uninterruptible Power System (UPS) units listed in the Scope section below with the HPE UPS Network Module Mini-slot Kit installed, in the HPE Network card GUI Shutdown Parameters screen, the "Switch On After Restart" settings can be set to 99999 seconds, but it may not stay at that value. When setting the "Switch on after the restart" value to 99999 seconds on the shutdown parameter screen, the value later may change to a lower value.Any value entered that is above 32000 seconds may change to an unpredictable number.
Any of the following HPE G4 Uninterruptible Power System (UPS) units with the HPE UPS Network Module Mini-slot Kit installed:HPE R/T2200 G4 NA/JP Uninterruptible Power SystemHPE R/T3000 G4 High Voltage INTL Uninterruptible Power SystemHPE R/T3000 G4 High Voltage NA/JP Uninterruptible Power SystemHPE R/T3000 G4 Low Voltage NA/JP Uninterruptible Power SystemHPE T1000 G4 INTL Uninterruptible Power SystemHPE T1000 G4 NA/JP Uninterruptible Power SystemHPE T1500 G4 INTL Uninterruptible Power SystemHPE T1500 G4 NA/JP Uninterruptible Power SystemHPE T750 G4 INTL Uninterruptible Power SystemHPE T750 G4 NA/JP Uninterruptible Power System
The value entered in the Shutdown Delay field should not be more than 32,000 seconds.NOTE:Products sold prior to the November 1, 2015 separation of Hewlett-Packard Company into Hewlett Packard Enterprise Company and HP Inc. may have older product names and model numbers that differ from current models.RECEIVE PROACTIVE UPDATES: Receive support alerts (such as Customer Advisories), as well as updates on drivers, software, firmware, and customer replaceable components, proactively via e-mail through HPE Subscriber's Choice. Sign up for Subscriber's Choice at the following URL:Proactive Updates Subscription Form.NAVIGATION TIP: For hints on navigating HPE.com to locate the latest drivers, patches, and other support software downloads for ProLiant servers and Options, refer to theNavigation Tips document.SEARCH TIP: For hints on locating similar documents on HPE.com, refer to theSearch Tips Document.
Operating Systems Affected:Not Applicable
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
BugZero Plan
Streamline upgrades with automated vendor bug scrubs
BugZero Prevent
Wish you caught this bug sooner? Get proactive today.