OPERATIONAL DEFECT DATABASE
...

...
Document VersionRelease DateDetails206/26/2019Added HPE Platinum 500W power supplies.106/29/2018Original Document Release.Some HPE ProLiant Gen10 servers configured in a single specific HPE Platinum 500W or 800W power configuration could reset or shut down under a heavy workloads of 50% (or more) when running early versions of the power supply firmware.If the power supply faults in a single or multi supply configuration, the system will log the following error messages in the Integrated Management Log (IML):Critical,20,2381,0x0014,System Error,0x0007,Other,04/25/201812:27:35:00,108:Server Critical Fault (Service Information: RuntimeFault System Board AUX/Main EFUSE (10h))ACTION: Gather necessaryinformation and create a support case using Active Health System Viewer(AHSV).And/OrCritical,18,2560,0x0014,System Error,0x0007,Other,04/25/201811:39:34:00,84:Server Critical Fault (Service Information: RuntimeFault, System Board, P12V Main/AUX Regulators (04h))ACTION: Gathernecessary information and create a support case using Active HealthSystem Viewer (AHSV).Critical,18,2566,0x0014,System Error,0x0007,Other,04/25/201811:39:34:00,85:Server Critical Fault (Service Information: RuntimeFault, Power Supply, Power Supply 1 (01h))ACTION: Gather necessaryinformation and create a support case using Active Health System Viewer(AHSV).IML Error messages:Critical,20,2381,0x0014,System Error,0x0007,Other,04/25/201812:27:35:00,108:Server Critical Fault (Service Information: RuntimeFault System Board AUX/Main EFUSE (10h)ACTION: Gather necessaryinformation and create a support case using Active Health System Viewer(AHSV).Critical,20,2387,0x0014,System Error,0x0007,Other,04/25/201812:27:35:00,109:Server Critical Fault (Service Information: RuntimeFault Power Supply Power Supply 1 (01h)ACTION: Gather necessaryinformation and create a support case using Active Health System Viewer(AHSV).
Some Platinum 500W (Model# HSTNS-PC40-1) and 800W (Model# HSTNS-PC41-1) power supplies with a CT#:XXXXXXX8JXXXXX and firmware version 1.01 (or earlier).Do Not replace the system board this will not change the failure mechanismFirmware power supply verification process: Use the HPE Integrated Lights-Out 5 (iLO 5) interface to verify the firmware on any HPE 500W or 800W Platinum power supplies installed in a suspect server configuration. Check the system information page for the power supply and verify the firmware currently installed. Boot to iLO 5 -> select system Information -> then power supplies. (See Figure 1 items bracketed in Green below):Figure 1:iLO 5 screenNot all 500W and 800w power supplies are affected, note digit 6 and digit 7 from the end of the Serial # for the supply. If the digits are 8J then check the firmware if the firmware is earlier than 1.02 upgrade the power supply firmware via the identified firmware process of choice in Service Action field below.Firmware below highlighted in Green below are modified 1.02 (fixed) firmware examples. The serial # and Firmware bracketed in Red is a firmware that needs to be updated via the component pack process (800W power supply shown below):Figure 2: Power Supply list in iLOAHS Power Supply Verification process:Use the AHS to verify the firmware on any 800W Platinum power supplies installed in a suspect server configuration. The Power supply CT number can be found in either the Dashboard or Static Tab information on the AHS screens. (See Figures 3 & 4 below, supply info bracketed in red are old firmware, items bracketed in Green show upgraded supply).Figure 3:Dashboard Tab viewFigure 4:Static Tab viewIf the power supply is out of the system any factory updated supply should have a Green dot on the Agency label on top of the supply (800W power supply shown below):Figure 5:Agency Label with Green dot indicating Factory Firmware reworkIf the power supply is installed in a server the modified supplies can be identified by a black dot on the rear fan cage of the power supply just above the 800w wattage label visible from the rear of the server (800W power supply shown below).Figure 6:Black Dot (ink/marker) on rear Fan Label indicating Factory Firmware rework
Upgrade any 500W or 800W Platinum power supply CT#:XXXXXXX8JXXXXX to firmware version 1.02 or later as follows:For Windows:cp031686.exehttps://downloads.hpe.com/pub/softlib2/software1/sc-windows-fw/p541281236/v125879/cp031686.exeFor Linux:firmware-powersupply-gen10powersupply-2018.06.21-1.1.x86_64.rpmhttps://downloads.hpe.com/pub/softlib2/software1/sc-linux-fw/p2018115667/v153652/RPMS/x86_64/firmware-powersupply-gen10powersupply-2018.06.21-1.1.x86_64.rpmAffected platform list:HPE ProLiant DL580 Gen10 ServerHPE ProLiant DL560 Gen10 ServerHPE ProLiant DL385 Gen10 ServerHPE ProLiant DL380 Gen10 ServerHPE ProLiant DL360 Gen10 ServerHPE ProLiant ML350 Gen10 ServerHPE ProLiant ML110 Gen10 ServerHPE ProLiant XL190r Gen10 ServerHPE ProLiant XL170r Gen10 ServerHPE Apollo 4510 SystemHPE Apollo r2800 Gen10 24 SFF Flexible Configure-to-order ChassisHPE Apollo r2600 Gen10 24 SFF Premium Configure-to-order ChassisHPE Apollo r2200 Gen10 12 LFF Configure-to-order Chassis
Operating Systems Affected:Not Applicable
No external links available for this bug
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
Bug Scrub Advisor
Streamline upgrades with automated vendor bug scrubs
BugZero Enterprise
Wish you caught this bug sooner? Get proactive today.