The server receives a shutdown request after the critical system inlet threshold alert is triggered in the SEL 2020-11-22 17:58:52 10567 SYS1001 The system is turning off. 2020-11-22 17:58:52 10566 SYS1003 System CPU Resetting 2020-11-22 17:58:49 10565 ISM0007 The iDRAC Service Module communication with iDRAC has ended. 2020-11-22 17:58:47 10564 RAC0704 Requested system powerdown 2020-11-22 17:58:44 10563 TMP0121 The system inlet temperature is greater than the upper critical threshold.
The shutdown is triggered by iDRAC as the critical temperature alert action was set to 'Power Off'. The System Inlet Temperature will not proactively shut down the system.
The recommended setting is ' No Action '. The setting can be changed using UI or racadm . UI: Configuration > System Settings > Alert Configuration > Alerts > Alert Configuration > "Enclosure Temp Probe" or "Temperature" racadm : racadm eventfilters set -c idrac.alert.system.tmp.critical -a none -n ipmi, snmp