This is not an issue but a guide on how to match the LSC_SIG number to the GPU Sled cold plate loop number. There are six leak sensors in the XE9680L: five on the GPU Sled one on the motherboard tray
This is working as design.
The following tables 1 and 2 show the correspondence between LifeCycle error messages (as shown in Figure 1) and H200/B200 GPU cold plate positions. Figure 1: LifeCycle error message Table 1: H200 Correspondence Table LSC_SIG H200 Cold plate positions LSC_SIG 1 Loop 1 (GPU Sled) LSC_SIG 2 Loop 5 (GPU Sled) LSC_SIG 3 Loop 4 (GPU Sled) LSC_SIG 4 Loop 3 (GPU Sled) LSC_SIG 5 Loop 2 (GPU Sled) LSC_SIG 8 Motherboard tray (Motherboard) Table 2: B200 Correspondence Table LSC_SIG B200 Cold plate positions LSC_SIG 1 Loop 5 (GPU Sled) LSC_SIG 2 Loop 4 (GPU Sled) LSC_SIG 3 Loop 3 (GPU Sled) LSC_SIG 4 Loop 2 (GPU Sled) LSC_SIG 5 Loop 1 (GPU Sled) LSC_SIG 8 Motherboard tray (Motherboard)