OPERATIONAL DEFECT DATABASE
...


...

On any of the HPE G2 Power Distribution Units (PDUs) listed in the Scope section below; the power outlets may be "ON," but the LED indicator may show "OFF" (or vice-versa). Sometimes the Power Distribution Units (PDU) cannot be configured, or the interface may be out-of-sync, requiring a power-cycle.A firmware programming code anomaly was found in firmware version 2.0.0.C through firmware version 2.0.0.N.
Any of the following HPE G2 Power Distribution Units (PDUs):HPE G2 Metered PDUsHPE G2 Metered 1.9kVA/IEC C20 Detachable 16A/120V Outlets (8) 5-20R/1U Horizontal NA/JP PDU (P9R45A)HPE G2 Metered 1.9kVA/IEC C20 Detachable 16A/120V Outlets (16) 5-20R/Vertical NA/JP PDU (P9R46A)HPE G2 Metered 2.8kVA/L5-30P 24A/120V Outlets (24) 5-20R/Vertical NA/JP PDU (P9R48A)HPE G2 Metered 2.8kVA/L5-30P 24A/120V Outlets (16) 5-20R/2U Horizontal NA/JP PDU (P9R49A)HPE G2 Metered 3.6kVA/IEC C20 Detachable 16A/100-240V Outlets (12) C13/1U Horizontal WW PDU (P9R50A)HPE G2 Metered Modular 4.9kVA/L6-30P 24A/208V Outlets (6) IEC C19/1U Horizontal NA/JP PDU (P9R51A)HPE G2 Metered 4.9kVA/L6-30P 24A/208V Outlets (12) C13 (4) C19/2U Horizontal NA/JP PDU (P9R52A)HPE G2 Metered 4.9kVA/L6-30P 24A/208V Outlets (32) C13 (6) C19/Vertical NA/JP PDU (P9R53A)HPE G2 Metered Modular 7.3kVA/60309 3-wire 32A/230V Outlets (6) C19/1U Horizontal INTL PDU (P9R54A)HPE G2 Metered 7.3kVA/60309 3-wire 32A/230V Outlets (12) C13 (4) C19/2U Horizontal INTL PDU (P9R55A)HPE G2 Metered 7.3kVA/60309 3-wire 32A/230V Outlets (32) C13 (6) C19/Vertical INTL PDU (P9R56A)HPE G2 Metered 8.3kVA/CS8265C 40A/208V Outlets (30) C13 (6) C19/Vertical NA/JP PDU (P9R57A)HPE G2 Metered 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13 (6) C19/Vertical NA/JP PDU (P9R58A)HPE G2 Metered 3Ph 8.6kVA/L21-30P 24A/208V Outlets (30) C13 (6) C19 (2) 5-20R/Vertical NA/JP PDU (P9R59A)HPE G2 Metered 3Ph 10kVA/CS8365C 35A/208V Outlets (30) C13 (6) C19/Vertical NA/JP PDU (P9R60A)HPE G2 Metered 3Ph 11kVA/60309 5-Wire 16A/230V Outlets (36) C13 (6) C19/Vertical INTL PDU (P9R61A)HPE G2 Metered Modular 8.3kVA/CS8265C 40A/208V Outlets (6) C19/1U Horizontal NA/JP PDU (P9R77A)HPE G2 Metered Modular 3Ph 8.6kVA/L15-30P 24A/208V Outlets (6) C19/1U Horizontal NA/JP PDU (P9R78A)HPE G2 Metered Modular 3Ph 11kVA/60309 5-wire 16A/230V Outlets (6) C19/1U Horizontal INTL PDU (P9R79A)HPE G2 Metered Modular 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (6) C19/1U Horizontal NA/JP PDU (P9R80A)HPE G2 Metered Modular 3Ph 22kVA/60309 5-wire 32A/230V Outlets (6) C19/1U Horizontal INTL PDU (P9R81A)HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (18) C13 (6) C19/Vertical NA/JP PDU (P9R82A)HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (36) C13 (12) C19/Vertical NA/JP PDU (P9R83A)HPE G2 Metered 3Ph 22kVA/60309 5-wire 32A/230V Outlets (18) C13 (6) C19/Vertical INTL PDU (P9R84A)HPE G2 Metered 3Ph 22kVA/60309 5-wire 32A/230V Outlets (36) C13 (12) C19/Vertical INTL PDU (P9R85A)HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU (P9R86A)HPE G2 Metered 3Ph 22kVA/60309 5-wire 32A/230V Outlets (12) C13 (12) C19/Vertical INTL PDU (P9R87A)HPE G2 Switched PDUsHPE G2 Switched 1.9kVA/IEC C20 Detachable 12A/120V Outlets (8) 5-20R/1U Horizontal NA/JP PDU (P9S07A)HPE G2 Switched 1.9kVA/IEC C20 Detachable 12A/120V Outlets (12) 5-20R/Vertical NA/JP PDU (P9S08A)HPE G2 Switched 2.8kVA/L5-30P 24A/120V Outlets (18) 5-20R/Vertical NA/JP PDU (P9S09A)HPE G2 Switched 2.8kVA/L5-30P 24A/120V Outlets (16) 5-20R/2U Horizontal NA/JP PDU (P9S10A)HPE G2 Switched 3.6kVA/IEC C20 Detachable 16A/100-240V Outlets (8) C13/1U Horizontal WW PDU (P9S11A)HPE G2 Switched 3.6kVA/IEC C20 Detachable 16A/100-240V Outlets (12) C13 (4) C19/Vertical WW PDU (P9S12A)HPE G2 Switched 4.9kVA/L6-30P 24A/208V Outlets (12) C13 (4) C19/2U Horizontal NA/JP PDU (P9S13A)HPE G2 Switched 4.9kVA/L6-30P 24A/208V Outlets (20) C13 (4) C19/Vertical NA/JP PDU (P9S14A)HPE G2 Switched 7.3kVA/60309 3-wire 32A/230V Outlets (12) C13 (4) C19/2U Horizontal INTL PDU (P9S16A)HPE G2 Switched 7.3kVA/60309 3-wire 32A/230V Outlets (20) C13 (4) C19/Vertical INTL PDU (P9S17A)HPE G2 Metered/Switched PDUsHPE G2 Metered/Switched 4.9kVA/L6-30P 24A/208V Outlets (20) C13 (4) C19/Vertical NA/JP PDU (P9S15A)HPE G2 Metered/Switched 7.3kVA/60309 3-wire 32A/230V Outlets (20) C13 (4) C19/Vertical INTL PDU (P9S18A)HPE G2 Metered/Switched 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13 (6) C19/Vertical NA/JP PDU (P9S19A)HPE G2 Metered/Switched 3Ph 11kVA/60309 5-wire 16A/230V Out (18) C13 (6) C19/Vertical INTL PDU (P9S20A)HPE G2 Metered/Switched 3Ph 14.4kVA/CS8365C 40A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU (P9S21A)HPE G2 Metered/Switched 3Ph 17.3kVA/60309 4-wire 48A/208V Out (12) C13 (12) C19/Vertical NA/JP PDU (P9S22A)HPE G2 Metered/Switched 3Ph 17.3kVA/60309 4-wire 48A/208V Out (36) C13 (12) C19/Vertical NA/JP PDU (P9S23A)HPE G2 Metered/Switched 3Ph 22kVA/60309 5-wire 32A/230V Out (12) C13 (12) C19/Vertical INTL PDU (P9S24A)HPE G2 Metered/Switched 3Ph 22kVA/60309 5-wire 32A/230V Out (36) C13 (12) C19/Vertical INTL PDU (P9S25A)Note:HPE high density model mounts on its side with outlets facing the back of the rack.
To resolve this issue, download and install the following firmware component:HPE G2 "Metered", "Switched", and "Metered and Switched" Power Distribution Units Firmware Version 2.0.0.PRECEIVE PROACTIVE UPDATES: Receive support alerts (such as Customer Advisories), as well as updates on drivers, software, firmware, and customer replaceable components, proactively in your e-mail through HPE Support Alerts. Sign up for Support Alerts at the following URL:HPE Email Preference CenterNAVIGATION TIP:For hints on navigating HPE.com to locate the latest drivers, patches and other support software downloads, refer to theNavigation Tips document.SEARCH TIP:For hints on locating similar documents on HPE.com, refer to theSearch Tips document.
Operating Systems Affected:Not Applicable
Click on a version to see all relevant bugs
Hewlett Packard Enterprise Integration
Learn more about where this data comes from
Bug Scrub Advisor
Streamline upgrades with automated vendor bug scrubs
BugZero Enterprise
Wish you caught this bug sooner? Get proactive today.