While upgrading PWR-4.4KW-DC-V3 FPD primary MCU upgrade failed and feeder will be down. Sometimes both the feeders( A / B ) corrupted and bring down the whole power module. Important Note : Whenever we go for the FPD we need to confirm both the feeders are present in the power module. If any of the feeder is missing / not connected then FPD upgrade will fail.
affected PID is PWR-4.4KW-DC-V3 trigger is upgrade power module fpd
no workaround or recovery action available
RP/0/RSP0/CPU0:IOSXR#show logging 0/RSP0/ADMIN0:Mar 5 04:27:09.733 WET: envmon[3901]: %INFRA-FPD_Driver-6-UPGRADE_RESULT : Upgrade completes 95 percent for fpd 0/PT0-PM0-DT-Pri0MCU@location 0/PT0. 0/RSP0/ADMIN0:Mar 5 04:27:18.660 WET: envmon[3901]: %INFRA-FPD_Driver-1-UPGRADE_ALERT : FPD 0/PT0-PM0-DT-Pri0MCU@0/PT0 image programming completed with UPGD FAIL state Info: [CRC mismatch detected for Pri0MCU upgraded firmware on 0/PT0/PM0, expected = 0x70e9, read = 0xb4fc] RP/0/RSP0/CPU0:IOSXR#show hw-module fpd Auto-upgrade:Enabled FPD Versions ============== Location Card type HWver FPD device ATR Status Running Programd ----------------------------------------------------------------------------------------- 0/BPID0 ASR-9010-DC-V2 1.0 CBC CURRENT 7.105 7.105 0/PT0 PWR-4.4KW-DC-V3 2.11 PM0-DT-Pri0MCU UPGD FAIL 3.00 3.00 <<<<<<<<<<< 0/PT0 PWR-4.4KW-DC-V3 2.11 PM0-DT-Pri1MCU CURRENT 3.01 3.01 0/PT0 PWR-4.4KW-DC-V3 2.11 PM0-DT-Sec054vMCU CURRENT 3.01 3.01 0/PT0 PWR-4.4KW-DC-V3 2.11 PM0-DT-Sec154vMCU CURRENT 3.01 3.01 0/PT0 PWR-4.4KW-DC-V3 2.11 PM0-DT-Sec5vMCU CURRENT 3.02 3.02 0/PT0 PWR-4.4KW-DC-V3 3.0 PM1-DT-Pri0MCU UPGD FAIL 3.01 3.01 <<<<<<<<<< 0/PT0 PWR-4.4KW-DC-V3 3.0 PM1-DT-Pri1MCU CURRENT 3.01 3.01 0/PT0 PWR-4.4KW-DC-V3 3.0 PM1-DT-Sec054vMCU CURRENT 3.01 3.01 0/PT0 PWR-4.4KW-DC-V3 3.0 PM1-DT-Sec154vMCU CURRENT 3.01 3.01 0/PT0 PWR-4.4KW-DC-V3 3.0 PM1-DT-Sec5vMCU CURRENT 3.02 3.02 0/PT1 PWR-4.4KW-DC-V3 3.0 PM0-DT-Pri0MCU CURRENT 3.01 3.01 0/PT1 PWR-4.4KW-DC-V3 3.0 PM0-DT-Pri1MCU CURRENT 3.01 3.01 0/PT1 PWR-4.4KW-DC-V3 3.0 PM0-DT-Sec054vMCU CURRENT 3.01 3.01 0/PT1 PWR-4.4KW-DC-V3 3.0 PM0-DT-Sec154vMCU CURRENT 3.01 3.01 0/PT1 PWR-4.4KW-DC-V3 3.0 PM0-DT-Sec5vMCU CURRENT 3.02 3.02 RP/0/RSP0/CPU0:IOSXR# Note : Whenever we go for the FPD we need to confirm both the feeders are present in the power module. If any of the feeder is missing / not connected then fpd upgrade will fail.